The snow, wind and seismic loads for a steel building anywhere in the United States come from ASCE 7, and the free ASCE Hazard Tool returns them for any address. The edition matters: the 2024 IBC uses ASCE 7-22, while the 2021 and 2018 IBC both use ASCE 7-16. Find out which IBC your state or city has adopted, pick the matching ASCE 7 edition in the tool, and your local building department's published values still have the final word.
The ASCE Hazard Tool asks for a "Standard Version" before it shows anything. The right answer depends on which edition of the International Building Code (IBC) your state or city enforces. Pick the wrong one and you get a real number for the wrong code.
| Your building code | Pick in the tool | What the snow number means |
|---|---|---|
| 2024 IBC | ASCE/SEI 7-22 | Strength level, already set for your risk category. There is no snow importance factor. To compare with an older allowable-stress number, multiply by 0.7. Example: Utah adopted the 2024 IBC on July 1, 2026. |
| 2021 IBC | ASCE/SEI 7-16 | The 2021 IBC still uses ASCE 7-16; only the IBC itself changed. Allowable-stress (50-year) ground snow, multiplied by an importance factor for your risk category. |
| 2018 IBC | ASCE/SEI 7-16 | Same standard and same snow basis as the 2021 IBC. Example: Idaho enforces the 2018 IBC statewide. |
| Older codes | ASCE/SEI 7-10 | Only for checking buildings designed under the 2012 or 2015 IBC. Not for a new building. |
| Existing buildings | ASCE/SEI 41-17 or 41-23 | Seismic evaluation and retrofit of existing buildings. Not for a new steel building. |
Not sure which IBC applies? Search for your city or county building department's "design criteria" or "building code" page. Most list the adopted code edition along with their minimum snow load, wind speed and frost depth. Code adoption happens state by state and sometimes city by city, so the building department is the reliable source.
Ground snow load (pg) in psf. This is not the roof load. Roof snow is calculated from it using roof slope, exposure, and whether the building is heated. Under ASCE 7-16 some mountain areas show "Case Study," which means the local building department's published value governs.
Basic wind speed in mph for your risk category. Both 7-16 and 7-22 give ultimate (strength-level) speeds, which are higher than the old 90 mph style numbers some older city pages still list. Exposure category (open country vs. town) is chosen separately for the design.
Spectral values (SDS, SD1) and the Seismic Design Category, A through F. Category D and above limit bracing choices and require ties between foundation piers, which affects cost.
Your building department has the final word. Many publish their own minimum snow, wind and frost depth, and some still list values from an older code. When the city's number and the map's number differ, the higher one usually governs. Residential-lot garages and shops permitted under a residential code (IRC) can follow a different snow basis; ask before you design. Utah specifics are on our Utah loads page.
Open the tool in a new tab, keep this page open, and follow the five steps above.
Send us the site, anywhere in the US, and we will return the ground snow, wind, seismic category and frost depth with the code basis, free. Every Tangent quote is engineered to those site-specific loads so the drawings get permitted and approved the first time.
The 2024 IBC uses ASCE/SEI 7-22. The 2021 IBC and the 2018 IBC both use ASCE/SEI 7-16. ASCE/SEI 7-10 belongs to the 2012 and 2015 IBC and is not for new buildings. Check your building department's design criteria page for the edition it enforces.
Yes. It is published by the American Society of Civil Engineers and returns snow, wind, seismic, ice, rain, flood, tsunami and tornado values for any US address without an account.
ASCE 7-22 snow loads are strength level and already include the reliability for your risk category, while older values were allowable-stress numbers multiplied by an importance factor. Multiply the 7-22 value by 0.7 to compare it with an older number. Some areas also genuinely went up when the maps were redrawn.
No. Roof snow is calculated from the ground snow load using roof slope, exposure, the thermal condition of the building and drift from adjacent roofs. The engineering for every Tangent building does this calculation for the actual site.
Yes, in all 50 states, to each state's adopted code. Send us the site and we will confirm the code edition and loads before quoting.
Updated November 2026. Sources: ASCE Hazard Tool (ascehazardtool.org); 2018, 2021 and 2024 International Building Code Chapter 16 and Chapter 35 referenced standards.